National Plumbing Code by Aedo Construction · RA 1378
NPC 2000
Visual Reference AEDO Main Site
Live: Chapters 1–14 · RA 1378 · NPC 2000 Edition
📐 National Plumbing Code — Philippines

NATIONAL PLUMBING CODE Philippines · RA 1378

The Revised National Plumbing Code of the Philippines governs all plumbing work in the country. This visual reference breaks down each chapter into clear rules, key dimensions, and illustrated diagrams — making the code readable for master plumbers, architects, civil engineers, and building officials.

📋 14 Chapters 📖 200+ Definitions 📏 Pipe Sizing & Grades 🔒 RLMP Requirement

Based on the Revised NPC (2000 Edition) under Republic Act No. 1378. Always verify against the official code for permit submissions.

13 Code
Chapters
2%
Min Drain
Grade ≤75mm
RLMP
Permit
Requirement
50mm
Min
Trap Seal
6 SETS
Plans per
Permit App.
All Chapters
Live
01
Administration
Sections 100–108 · 9 Sections
  • Permit requirements & who can apply
  • Plans signed & sealed by RLMP (6 sets)
  • Inspection types & inspector qualifications
  • Connection approval — permanent & temporary
Read Chapter →
Live
02
Definitions
Sections 201–202 · 200+ Terms
  • Searchable glossary of all plumbing terms
  • Trap, trap arm, trap seal defined
  • Drainage, vent & supply system terms
  • Fixture unit, branch interval, grade
Read Chapter →
Live
03
General Regulations
Sections 301–314 · 14 Sections
  • Pipe grade: 2% for ≤75mm, 1% for >75mm
  • Acceptable fittings for direction changes
  • Rodent proofing at pipe penetrations
  • Approved pipe materials & standards
Read Chapter →
Live
04
Plumbing Fixtures
Sections 401–411 · 11 Sections
  • Fixture material & surface requirements
  • Clearances: 750mm front, 150mm side (WC)
  • Floor drain trap seal & strainer standards
  • Minimum fixtures by occupancy — full table
Read Chapter →
Live
05
Water Supply & Distribution
Sections 501–513 · 13 Sections
  • Cross-connection control & air gap requirements
  • Pipe sizing by Water Supply Fixture Units (WSFU)
  • PRV required when pressure > 550 kPa
  • Hot water max 60°C; shower limit 49°C
Read Chapter →
Live
06
Sanitary Drainage
Sections 601–620 · 20 Sections
  • DFU values for every fixture type
  • Horizontal branch & stack sizing tables
  • Building drain sizing by grade
  • Sumps, garage drains & indirect wastes
Read Chapter →
Live
07
Vent Piping
Sections 701–715 · 15 Sections
  • Why venting protects trap seals
  • Max trap-to-vent distances (Table 7-1)
  • Individual, wet, common & circuit vents
  • AAV rules & yoke vents for high-rise
Read Chapter →
Live
08
Traps, Cleanouts & Backwater Valves
Sections 801–813 · 13 Sections
  • Trap seal depth: 50–100mm required
  • Prohibited traps (S-trap, drum, running)
  • Cleanout spacing: max 15m horizontal
  • Backwater valves for below-grade drainage
Read Chapter →
Live
09
Plumbing Specialties
Sections 901–912 · 12 Sections
  • Grease interceptors for commercial kitchens
  • Oil & sand interceptors (parking/workshops)
  • Clothes washer standpipe: 600–900mm
  • AC condensate: indirect waste required
Read Chapter →
Live
10
Septic Tanks
Sections 1001–1012 · 12 Sections
  • Tank sizing by DFU load
  • Setback distances from structures & wells
  • Absorption field design & soil testing
  • Dosing chambers & subsurface disposal
Read Chapter →
Live
11
Storm Drainage
Sections 1101–1110 · 10 Sections
  • Roof drain sizing by rainfall intensity
  • Leaders, conductors & area drains
  • Storm & sanitary separation requirement
  • Subsoil drainage & sump pumps
Read Chapter →
Live
12
House Drains & House Sewers
Sections 1201–1212 · 12 Sections
  • Public-sewer connection & 61m availability rule
  • Materials, under-slab & 1.5m/0.6m clearances
  • Min 102mm size & 2% slope matrix (Table 12-2)
  • Water-pipe trench isolation & abandoned sewers
Read Chapter →
Live
13
Joints & Connections
Sections 1301–1308 · 8 Sections
  • Gas/watertight joints & reaming
  • Caulked, threaded, wiped, soldered & solvent joints
  • Connecting dissimilar materials (adapters/unions)
  • Slip/expansion & prohibited joints
Read Chapter →
Live
14
Quality & Weights of Materials
Materials & Referenced Standards
  • Factory marking & material quality (Table 14-4)
  • Copper types & color-stripe codes (K/L/M/DWV)
  • Ferrule & bushing tables (14-1, 14-2)
  • Closet rings, cleanouts & drainage valves
Read Chapter →
About This Reference

Why Use This Visual Reference?

The official National Plumbing Code is dense legal text. This site presents each section with clear language, illustrated diagrams, dimension tables, and key requirement callouts — so you spend less time decoding and more time designing.

📐 Technical SVG diagrams for spatial requirements
📋 Tables showing dimensions at a glance
🔍 Searchable glossary of 200+ plumbing terms
📱 Mobile-ready for field and site use

Important: This reference is for educational purposes. Always cross-check with the official Revised National Plumbing Code of the Philippines (RA 1378, 2000 Edition) and consult a Registered and Licensed Master Plumber for permit submissions and construction decisions.