National Plumbing Code Chapter 6 β€” Sanitary Drainage
NPC 2000
← All Chapters Ch. 5: Water Supply Ch. 7: Vent Piping β†’
Chapter 6 Β· Sections 601–620
πŸ”© Sanitary Drainage

Sanitary Drainage

Chapter 6 is the heart of drain design β€” it establishes the Drainage Fixture Unit (DFU) system for calculating pipe sizes, defines the sizing tables for horizontal branches, vertical stacks, and the building drain, and regulates special conditions like below-grade sumps, garage drains, and indirect wastes from equipment. Mastering this chapter allows you to size every drain pipe in a building from scratch.

πŸ”’ DFU Fixture Demand πŸ“ Drain Pipe Sizing Tables πŸ—οΈ Stack Design Rules πŸ’¦ Sump & Ejector Pumps
Β§ 601

Scope

What the sanitary drainage chapter covers

Chapter 6 applies to all sanitary drainage piping within a building β€” from the fixture trap outlet to the point of connection with the public sewer or approved private disposal system. It covers:

Storm drainage (roof drains, area drains, gutters) is intentionally excluded from this chapter β€” see Chapter 11 for storm drainage. Storm and sanitary systems shall be completely separate unless specifically approved by the local authority.
Sanitary Drainage Systems β€” Design and Installation (NPC Β§702)

Sanitary (excreta) drainage system β€” design & installation. Every fixture trap discharges through properly sized, graded, and vented drain piping to the building drain and house sewer. Pipe is sized by drainage fixture units (DFU); minimum grade is 2% (20 mm/m) for ≀75 mm and 1% (10 mm/m) for β‰₯100 mm, with cleanouts at the required points and storm water kept completely separate. (NPC Β§702)

Β§ 602

Design of Drainage System

Fundamental design principles

Gravity Drainage Preferred
Every fixture shall discharge to a gravity drainage system wherever possible. Pumped (ejector) systems are only permitted where gravity drainage is physically impossible.
Separate Systems
Every building with plumbing fixtures shall have a complete, separate sanitary drainage system. Two adjacent buildings shall not share a drainage system inside either building.
Self-Cleaning Velocity
Drain pipes shall be sized and graded to maintain a minimum flow velocity of 0.6 m/s (2 fps) β€” the minimum velocity to keep solids in suspension and prevent deposits.
No Trap-to-Trap Connections
Fixture drains shall not connect to another fixture's trap arm or tailpiece β€” each fixture requires its own trap connection to the drain branch.
Pipe Fitting Interior – Smooth Waterway and Recessed Drainage Threads (NPC 701.3)

Drainage fittings shall have a smooth interior waterway with no burrs or obstructions and recessed threads providing a 2% slope (21mm/m) toward the flow. Standard flat threads (no recess) create a shoulder obstruction that traps debris and causes turbulence β€” prohibited in drain lines.

Β§ 603

Underground Drainage Pipe

Approved materials and installation for below-slab drain piping

Material Approved For Underground? Notes
Cast Iron (hub-and-spigot or no-hub) βœ“ Yes Most durable; preferred for building drain under slab
PVC-DWV (Schedule 40 or SDR35) βœ“ Yes Most common in Philippine construction; solvent-welded joints
Vitrified Clay (VC) βœ“ Yes For building sewer (outside building) only; coupled joints
ABS-DWV βœ“ Yes Where approved by local authority
Galvanized Steel/Iron βœ— No Corrodes rapidly when buried; prohibited underground
Copper (DWV) ⚠ Limited Permitted but cost-prohibitive; requires insulation from concrete (alkali attack)
Embedment: Underground PVC drain pipes shall be embedded in clean granular material (sand or pea gravel) for a minimum of 100mm above and below the pipe. No sharp rocks or fill containing debris in contact with the pipe. Minimum cover over the pipe: 300mm under driveways and parking areas; 150mm under landscaped areas.
Galvanized Pipe Height Restriction Above Ground (NPC Β§700)

Galvanized steel or wrought iron pipe shall NOT be used underground for drainage. Transition to an approved underground material (cast iron, PVC-DWV, ABS-DWV) at least 152mm above finished ground level. Correct: galvanized pipe used only above grade; Incorrect: galvanized pipe running underground β€” causes rapid corrosion and pipe failure.

Vitrified Clay Pipe – Underground Only (NPC 701.2)

Vitrified clay pipe is permitted for underground gravity drainage only β€” never above ground or for pressurized (ejector) systems. Minimum 300mm cover below finished ground level. Clay is a brittle material and must be protected from loads, vibration, and settlement.

LOOKUP

Underground Pipe Material Lookup

Select a pipe material to check if it is approved for underground drainage use per Β§603.

Β§603 Underground Status
Β§ 604

Grade and Support of Drainage Pipe

Slope and hanger spacing for horizontal drain piping

Grade Rule (from Β§309): ≀75mm pipes β€” minimum 2% grade (20mm drop per 1,000mm run). β‰₯100mm pipes β€” minimum 1% grade (10mm drop per 1,000mm run).
Pipe Size Min Grade Drop per Meter Max Hanger Spacing
32 mm (1ΒΌ") 2% 20 mm/m 1,200 mm
38 mm (1Β½") 2% 20 mm/m 1,200 mm
50 mm (2") 2% 20 mm/m 1,500 mm
75 mm (3") 2% 20 mm/m 1,500 mm
100 mm (4") 1% 10 mm/m 1,800 mm
150 mm (6") 1% 10 mm/m 2,400 mm
200 mm (8") and above 1% 10 mm/m 3,000 mm
Excessive Grade is Also Prohibited: A slope steeper than 45Β° (other than for a vertical stack) is prohibited in horizontal drain runs β€” the liquid races ahead and leaves solids behind, causing blockage. Maximum grade: 45Β°. For grades beyond 45Β°, the pipe is classified as a vertical stack.
Pipe Hangers and Supports – Spacing Requirements (NPC 705.3)

Maximum hanger spacing for horizontal pipes: steel pipe Β½"–2" = 8ft (2.4m); copper pipe Β½"–1" = 6ft (1.8m); plastic pipe (PVC/CPVC/PEX) = 2.5ft (0.75m) for Β½"–1", up to 4ft (1.2m) for larger sizes; cast iron = 5ft (1.5m) for 1Β½"–2", up to 10ft (3.0m) for 8"–12". Vertical pipes shall be supported at each floor level.

CALCULATOR

Drain Grade & Drop Calculator

Enter pipe size and horizontal run length to find the minimum invert drop and maximum hanger spacing per Β§604.

Grade Requirements
Β§ 605

Drainage Fixture Unit (DFU) Values

Table 6-1 β€” Drainage demand load for each fixture type

What is a DFU? One Drainage Fixture Unit = a drain flow of approximately 28.3 L/min. DFU values account for both flow rate and frequency of use. Sum the DFUs of all fixtures to size branches, stacks, and the building drain using Table 6-2 (Β§606).
Fixture Trap Size (mm) DFU Value Min Branch Drain Size (mm)
Bathtub38238
Bidet38238
Clothes Washer (domestic)51251
Dental Unit / Cuspidor32132
Dishwasher / Sink (residential)38238
Drinking Fountain32132
Floor Drain51251
Interceptor β€” grease / oil51351
Interceptor β€” sand / auto wash76676
Kitchen Sink (domestic)38238
Lavatory / Wash Basin (single)32132
Wash Basins (in sets)38238
Laundry Tub38238
Service Sink51351
Sink β€” commercial / industrial / school38351
Sink β€” clinic (flushing rim)766100
Shower (single stall)51251
Urinal β€” stall / wall (washout)38–51251
Urinal β€” pedestal / blowout / syphon-jet76676
Water Closet β€” private installation764100
Water Closet β€” public installation766100

Note: The minimum branch drain size is governed by the fixture trap size β€” a pipe shall never be smaller than the trap it serves. A WC drain is always minimum 100mm regardless of its 75mm trap.

Table 7-2 Visual Fixture DFU Chart (NPC 702.1 / Table 7-2)

Visual DFU reference (per NPC Table 7-2): Lavatory / Drinking Fountain / Dental Unit = 1 DFU (32 mm trap); Bathtub / Bidet / Laundry Tub / Kitchen Sink / Dishwasher = 2 DFU (38 mm trap); Shower / Clothes Washer / stall Urinal = 2 DFU (51 mm trap); Water Closet β€” private = 4 DFU, public = 6 DFU (76 mm trap). Use the minimum trap size shown for each fixture.

Continuous Flow Outlet – 2 FU per 0.063 L/s (1 GPM) Rule (NPC 702.2)

For continuous flow outlets (sump pumps, A/C condensate lines, etc.), fixture units are calculated at 2 FU per 0.063 L/s (1 GPM) of discharge. Examples: 0.063 L/s = 2 FU; 0.126 L/s = 4 FU; 0.189 L/s = 6 FU; 0.252 L/s = 8 FU; 0.315 L/s = 10 FU. Do not reduce pipe size below the outlet size of the discharging device.

Table 7-3 – Unlisted Fixture Units by Discharge Rate (NPC 702.2 / Table 7-3)

For fixtures not in Table 7-2, assign DFU based on discharge flow rate: ≀ 0.47 L/s (7.5 GPM) = 1 FU; 0.50–0.95 L/s (8–15 GPM) = 2 FU; 1.00–1.89 L/s (16–30 GPM) = 4 FU; 1.95–3.15 L/s (31–50 GPM) = 6 FU. Use the higher (next) FU value when flow falls between two ranges.

Maximum Trap Loading – Pipe Size vs Maximum FU (NPC 702.1)

Maximum trap loading by pipe size: 32mm (1ΒΌ") = 1 FU; 38mm (1Β½") = 3 FU; 51mm (2") = 4 FU; 76mm (3") = 6 FU; 102mm (4") = 8 FU. The combined DFU connected to any trap, trap arm, or horizontal branch shall not exceed these values for the corresponding pipe size.

CALCULATOR

DFU Demand Counter

Add fixtures to tally total Drainage Fixture Units. Use the total with the Β§606 Drain Pipe Sizer below.

No fixtures added yet.
Total DFU Demand
Β§ 606

Drain Pipe Sizing

NPC Table 7-5 β€” Maximum fixture-unit loading & length of excreta drainage and vent piping

Table 7-5 β€” Maximum Fixture-Unit Loading & Maximum Length (Excreta Drainage & Vent Piping)

Pipe Size Max FU β€” Vertical Drain Max FU β€” Horizontal Drain / Branch Max Length β€” Vertical (m) Max FU β€” Vent Max Length β€” Vent (m)
32 mm (1ΒΌ")1114114
38 mm (1Β½")2 (2)2208 (3)18
51 mm (2")16 (3)8 (3)262437
65 mm (2Β½")32 (3)14 (3)454855
76 mm (3")48 (4)35 (4)658465
102 mm (4")256216 (5)9125691
127 mm (5")600428 (5)119600119
152 mm (6")1,380720 (5)1551,380155
203 mm (8")3,6002,640 (5)2283,600228
254 mm (10")5,6004,680 (5)β€”β€”β€”

Notes (per NPC Table 7-5): (1) Excluding trap arm  β€’  (2) Except sinks, urinals, and dishwashers  β€’  (3) Except 6-fixture-unit traps or water closets  β€’  (4) Only four (4) water closets or six (6) fixture-unit traps are allowed on any vertical pipe or stack; not more than three (3) water closets or six (6) fixture-unit traps on any horizontal branch or drain  β€’  (5) Horizontal values are based on a 2% (20.9 mm/m) slope. At a 1% (10.4 mm/m) slope, multiply the horizontal fixture-unit value by a factor of 0.8.
Horizontal drainage piping has no length limit. A vent shall not be smaller than 32 mm nor less than Β½ the diameter of the drain to which it connects; fixture-unit load values for drainage and vent piping are computed from Tables 7-2 and 7-3, not to exceed β…“ the total permitted vent length. When vents are increased one pipe size for their entire length, the maximum-length limits in this table do not apply.

Drain, Waste, and Vent Pipe Sizing – Minimum Diameters (NPC 706.2 & Table 706.2)

Minimum pipe diameters for drain, waste, and vent pipes based on total fixture units: 1–2 DFU = 1ΒΌ" (32mm); 3–10 DFU = 1Β½" (38mm); 11–20 DFU = 2" (51mm); 21–60 DFU = 3" (76mm); 61–216 DFU = 4" (102mm). Vent pipes: individual fixture vents minimum 1ΒΌ"; common vents (2+ fixtures) refer to sizing table. Vent pipe diameter shall not be less than half the required drain diameter it serves.

CALCULATOR

Drain & Vent Pipe Sizer β€” Table 7-5

Enter the total fixture-unit (FU/DFU) load and choose the piping function to find the minimum pipe size and maximum length per NPC Table 7-5. Use the DFU Counter in Β§605 above for your total.

Required Minimum Pipe Size β€” Table 7-5
Drainage and Vent System Water Test Setup

Drainage and vent water test: plug all openings, fill system to the highest point (overflow). Hold for minimum 15 minutes β€” water level must not drop. For sectional testing, maintain minimum 3-metre water head above the section being tested, with upper 3 metres of previous section included in the next test.

Β§ 607

Offsets in Soil and Waste Stacks

How to handle changes in direction on vertical drainage stacks

Offset Angle Requirement Notes
≀ 45Β° from vertical No change in stack size required at offset Treated as continuation of stack; use long-radius fittings
> 45Β° from vertical (nearly horizontal) Size offset as a horizontal drain using Table 6-2 The offset and both vertical segments above/below may need enlarging
Any offset > 45Β° Cleanout required at change of direction Accessible cleanout fitting at each end of the offset
Key Rule: Fixtures shall not connect to a stack within 600mm above or below an offset greater than 45Β°. Connections within this zone are treated as being on separate branch intervals for sizing purposes.
LOOKUP

Stack Offset Requirements

Select the offset angle from vertical to see the requirements per Β§607.

Β§607 Requirements
Β§ 608

Branch Intervals

Definition and use of branch intervals in stack sizing

Branch Interval Definition: A length of soil or waste stack corresponding to a storey height, but not less than 2,400mm (2.4m), within which the horizontal branches from one floor level connect to the stack.

Branch intervals are used to count floors on a stack. The "maximum DFU per branch interval" column in Table 6-2 limits how many fixtures can connect at any single floor level β€” preventing overloading of the short section of stack between two consecutive floor connections.

Standard 3m Floor-to-Floor
A standard Philippine residential floor height of ~3.0m = 1 branch interval. If two toilets are on the same floor, their combined DFU must not exceed the "per-interval" limit for that stack size.
Yoke Venting Trigger
Stacks serving 10 or more branch intervals require yoke vents at every 10th interval (see Chapter 7 Β§712). A 10-storey building with 3m floors = 10 branch intervals = yoke vent required.
Β§ 609

Building Drain

Definition, starting point, and sizing of the building horizontal drain

Definition: The building drain is the lowest horizontal piping of the drainage system that receives waste from soil and waste stacks and conveys it by gravity to the building sewer. It begins at the point 0.6m (2 feet) inside the outer face of the building foundation wall.
Building Drain Requirement Specification
Starting point 0.6m inside outer face of foundation wall
Minimum size 100mm (4") β€” cannot be smaller than the largest stack it receives
Minimum grade 1% (10mm per meter) β€” or 2% where space permits
Cleanout at base of each stack Required within 300mm of base β€” accessible
Cleanout at 90Β° changes of direction Required wherever a branch exceeds 45Β° horizontal turn
Cleanout spacing (building drain) Maximum 15m apart (for 100mm pipe); 30m for β‰₯150mm
CHECKER

Building Drain Compliance Checker

Enter building drain specifications to verify compliance with Β§609 requirements.

Compliance Results
Β§ 610

Sump Pits and Ejector Pumps

Drainage for below-grade areas that cannot drain by gravity

Where plumbing fixtures are located below the level of the next upstream manhole cover on the public sewer, or where gravity drainage to the building drain is not possible, a sewage sump pit with ejector pump shall be installed.

Requirement Specification
Sump pit material Pre-cast concrete, fiberglass, or polyethylene β€” watertight and gastight
Sump pit minimum size 450mm diameter Γ— 600mm depth (for residential); larger for commercial
Cover Gastight, removable cover β€” prevents sewer gas release
Ejector pump Submersible sewage pump with automatic float switch; duplex (2 pumps) for critical applications
Discharge pipe Check valve required on discharge to prevent backflow when pump stops
Alarm High-water alarm required for commercial/residential buildings with occupied below-grade spaces
Vent pipe Sump pit shall be vented through a pipe extended outdoors or connected to building vent system
CHECKER

Sump Pit & Ejector Requirements

Select the application type to see minimum specifications per Β§610.

Minimum Requirements
Β§ 611

Garage Floor Drains

Oil interceptor requirements for vehicle service areas

Required: Floor drains in garages, service stations, car washes, and any area where vehicle fluids (oil, fuel, antifreeze) may enter the drain shall discharge through an approved oil/sand interceptor before connecting to the sanitary drainage system.
Β§ 612

Indirect Waste Piping

Equipment that must discharge through an air gap into the drain system

Why Indirect Waste? Certain equipment β€” if directly connected to the drain β€” could allow sewer gas or backflow contamination into the equipment. An indirect connection via air gap physically breaks the connection between the equipment drain and the sanitary system.
Equipment / Device Indirect Waste Required? Recommended Receptor
Air conditioning condensate drain Yes Floor drain, sink, or approved receptor with air gap
Refrigerator / ice maker drain Yes Floor drain or open receptor
Commercial steamer / steam cooker Yes Floor sink or floor drain receptor
Dishwasher (commercial) Yes Floor sink or trapped receptor β€” air gap at sink drain
Domestic dishwasher Air break High loop or air gap fitting at sink drain connection
Drinking fountain waste Yes Floor drain with air gap at fountain outlet
Pressure relief valve discharge Yes Open sight drain β€” terminates above floor drain or outside
LOOKUP

Indirect Waste Requirement Lookup

Select the equipment type to check if an indirect waste connection is required per Β§612.

Β§612 Indirect Waste Status
Β§ 613

Special Wastes

Industrial, chemical, and hazardous waste disposal rules

Prohibited: Industrial waste containing acids, strong alkalis, oil, grease, flammable materials, or toxic substances shall not be discharged directly into the sanitary drainage system without prior treatment or neutralization.
Waste Type Required Treatment
Acid waste (laboratories, clinics) Dilution/neutralization pit β€” pH 6–10 required before discharge
Grease-laden waste (commercial kitchens) Grease interceptor sized per anticipated flow β€” see Chapter 9
Radioactive waste (hospitals, research) Special holding tank β€” must comply with PNRI (Philippine Nuclear Research Institute) regulations
Infectious waste (hospitals) Disinfection/sterilization required; DOH-compliant disposal
Photographic/X-ray waste (silver compounds) Silver recovery unit required before discharge
LOOKUP

Special Waste Treatment Lookup

Select the waste type to see the required pre-treatment before discharge per Β§613.

Required Pre-Treatment
← Chapter 5: Water Supply Chapter 7: Vent Piping β†’ All Chapters